8-53 Start SelectOption: Function:[2] Logic AND Activates Start command via the fieldbus/serialcommunication port, AND additionally via oneof the digital inputs.[3] * Logic OR Activates Start command via the fieldbus/serialcommunication port OR via one of the digitalinputs.8-54 Reversing SelectOption: Function:[0] DigitalinputSelect control of the frequency converterreverse function via the terminals (digitalinput) and/or via the fieldbus.[1] Bus Activates the Reverse command via the serialcommunication port or fieldbus option .[2] Logic AND Activates the Reverse command via thefieldbus/serial communication port, ANDadditionally via one of the digital inputs.[3] * Logic OR Activates the Reverse command via thefieldbus/serial communication port OR via oneof the digital inputs.8-55 Set-up SelectOption: Function:Select control of the frequency converter set-up selection via the terminals (digital input)and/or via the fieldbus.[0] DigitalinputActivates the set-up selection via a digitalinput.[1] Bus Activates the set-up selection via the serialcommunication port or fieldbus option.[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionallyvia one of the digital inputs.[3] * Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of thedigital inputs.8-56 Preset Reference SelectOption: Function:Select control of the frequency converterPreset Reference selection via the terminals(digital input) and/or via the fieldbus.[0] DigitalinputActivates Preset Reference selection via adigital input.[1] Bus Activates Preset Reference selection via theserial communication port or fieldbus option.[2] Logic AND Activates Preset Reference selection via thefieldbus/serial communication port, ANDadditionally via one of the digital inputs.8-56 Preset Reference SelectOption: Function:[3] * Logic OR Activates the Preset Reference selection via thefieldbus/serial communication port OR via oneof the digital inputs.6.2 Parameter Group 12-**6.2.1 12-0* IP Settings12-00 IP Address AssignmentOption: Function:Selects the IP Address assignment method.[0] * Manual IP-address can be set in12-01 IP Address IP Address.[1] DHCP IP-address is assigned via DHCP server.[2] BOOTP IP-address is assigned via BOOTP server.12-01 IP AddressRange: Function:[000.000.000.000 -255.255.255.255]Configure the IP address of theoption. Read-only if 12-00 IP AddressAssignment set to DHCP or BOOTP.12-02 Subnet MaskRange: Function:[000.000.000.000 -255.255.255.255]Configure the IP subnet mask of theoption. Read-only if 12-00 IP AddressAssignment set to DHCP or BOOTP.12-03 Default GatewayRange: Function:[000.000.000.000 –255.255.255.255]Configure the IP default gateway ofthe option. Read-only if 12-00 IPAddress Assignment set to DHCP orBOOTP.12-04 DHCP ServerRange: Function:[000.000.000.000 –255.255.255.255]Read only. Displays the IP addressof the found DHCP or BOOTPserver.NOTEA power-cycle is necessary after setting the IP parametersmanually.12-05 Lease ExpiresRange: Function:Application dependent* [Application dependant]Parameters MCA 121 EtherNet/IPMG.90.J3.02 - VLT® is a registered Danfoss trademark 316 6