5.2.7 Ordering Numbers: Harmonic FiltersHarmonic filters are used to reduce mains harmonics.• AHF 010: 10% current distortion• AHF 005: 5% current distortionCooling and ventilationIP20: Cooled by natural convection or with built-in fans. IP00: Additional forced cooling is required. Sufficient airflowthrough the filter must be secured during installation to prevent overheating of the filter. Airflow of minimum 2 m/s isrequired through the filter.Power and CurrentRatingsTypicalmotorFilter current rating Ordering no AHF005 Ordering no AHF01050 Hz[kW] [A]* [kW] [A] IP00 IP20 IP00 IP20PK37-P4K0 1,2-9 3 10 130B1392 130B1229 130B1262 130B1027P5K5-P7K5 14,4 7,5 14 130B1393 130B1231 130B1263 130B1058P11K 22 11 22 130B1394 130B1232 130B1268 130B1059P15K 29 15 29 130B1395 130B1233 130B1270 130B1089P18K 34 18,5 34 130B1396 130B1238 130B1273 130B1094P22K 40 22 40 130B1397 130B1239 130B1274 130B1111P30K 55 30 55 130B1398 130B1240 130B1275 130B1176P37K 66 37 66 130B1399 130B1241 130B1281 130B1180P45K 82 45 82 130B1442 130B1247 130B1291 130B1201P55K 96 55 96 130B1443 130B1248 130B1292 130B1204P75K 133 75 133 130B1444 130B1249 130B1293 130B1207P90K 171 90 171 130B1445 130B1250 130B1294 130B1213Table 5.16 380-415 V, 50 Hz* HO ratingsPower and CurrentRatingsTypicalmotorFilter current rating Ordering no AHF005 Ordering no AHF01050 Hz[kW] [A]* [kW] [A] IP00 IP20 IP00 IP20PK37-P4K0 1,2-9 3 10 130B3095 130B1257 130B2874 130B2262P5K5-P7K5 14,4 7,5 14 130B3096 130B2858 130B2875 130B2265P11K 22 11 22 130B3097 130B2859 130B2876 130B2268P15K 29 15 29 130B3098 130B2860 130B2877 130B2294P18K 34 18,5 34 130B3099 130B2861 130B3000 130B2297P22K 40 22 40 130B3124 130B2862 130B3083 130B2303P30K 55 30 55 130B3125 130B2863 130B3084 130B2445P37K 66 37 66 130B3026 130B2864 130B3085 130B2459P45K 82 45 82 130B3127 130B2865 130B3086 130B2488P55K 96 55 96 130B3128 130B2866 130B3087 130B2489P75K 133 75 133 130B3129 130B2867 130B3088 130B2498P90K 171 90 171 130B3130 130B2868 130B3089 130B2499Table 5.17 380-41 5V, 60 Hz* HO ratingsHow to Order VLT® AutomationDrive FC 300 Design Guide, 0.25-75 kW102 MG33BE02 - VLT® is a registered Danfoss trademark55RSPSupply - 1-888-532-2706 - www.RSPSupply.comhttp://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx