FC 300 Design GuideHow to Programme" Parameters: DriveInformation" 15-0* Operating DataParameter group containing operating data e.g.Operating Hours, kWh counters, Power Ups etc.15-00 Operating HoursRange:0 - 2147483647 h *0hFunction:Indicates how long the frequency converter has run.The value is saved when the unit is turned off.15-01 Running HoursRange:0 - 2147483647 h * 0hFunction:Indicates how many hours the motor has run.Reset counter in par. 15-07. The value issaved when the unit is turned off.15-02 kWh CounterRange:0 - 2147483647 kWh * 0kWhFunction:States the power consumption from mains inkWh as a mean value over one hour. Resetcounter: Par. 15-06.15-03 Power Up'sRange:0 - 2147483647 *0Function:States the number of power-ups to thefrequency converter.15-04 Over Temp'sRange:0 - 65535 *0Function:States the number of temperature faults onthe frequency converter.15-05 Over Volt'sRange:0 - 65535 *0Function:States the number of overvoltages on thefrequency converter.15-06 Reset kWh CounterOption:*Do not reset [0]Reset counter [1]Function:Reset to zero of kWh hour counter (par. 15-02).Reset the kWh counter by selecting Reset [1] andpressing [OK]. You cannot select this parametervia the serial port, RS 485.NB!:The reset is carried out by pressing [OK].15-07 Reset Running Hours CounterOption:*Do not reset [0]Reset counter [1]Function:Resets the running hours counter tozero (par. 15-01).Reset the running hours counter by selecting Reset[1] and pressing [OK]. You cannot select thisparameter via the serial port, RS 485." 15-1* Data Log SettingsThe Data Log enables continuous logging of upto 4 data sources (par. 15-10) at individualrates (par. 15-11). A trigger event (par. 15-12)and window (par. 15-14) are used to start andstop the logging conditionally.15-10 Logging SourceArray [4]Option:None16-00 Control Word16-01 Reference [Unit]16-02 Reference %16-03 Status Word16-10 Power [kW]16-11 Power [hp]16-12 Motor Voltage16-13 Frequency16-14 Motor Current16-16 Torque16-17 Speed [RPM]* default setting ( ) display text [ ] value for use in communication via serial communication port208 MG.33.B4.02 - VLT is a registered Danfoss trademark