3.17 Parameters: Data Read-outs3.17.1 16-** Data ReadoutsParameter group for data read-outs, e.g. actual references, voltages, control, alarm, warning and status words.3.17.2 16-0* General StatusParameters for reading the general status, e.g. the calculated reference, the active control word, status.16-00 Control WordRange: Function:0 N/A* [0 - 65535 N/A] View the Control word sent from the frequency converter via the serial communication port in hexcode.16-01 Reference [Unit]Range: Function:0.000 Ref-erenceFeed-backUnit*[-999999.000 - 999999.000 Refer-enceFeedbackUnit]View the present reference value applied on impulse or analog basis in the unit resulting from theconfiguration selected in par. 1-00Configuration Mode (Hz, Nm or RPM).16-02 Reference [%]Range: Function:0.0 %* [-200.0 - 200.0 %] View the total reference. The total reference is the sum of digital, analog, preset, bus, and freezereferences, plus catch-up and slow-down.16-03 Status WordRange: Function:0 N/A* [0 - 65535 N/A] View the Status word sent from the frequency converter via the serial communication port in hexcode.16-05 Main Actual Value [%]Range: Function:0.00 %* [-100.00 - 100.00 %] View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value.16-09 Custom ReadoutRange: Function:0.00 Cus-tomReadou-tUnit*[0.00 - 0.00 CustomReadoutUnit] View the value of custom readout from par. 0-30Unit for User-defined Readout to par. 0-32CustomReadout Max Value3.17.3 16-1* Motor StatusParameters for reading the motor status values.16-10 Power [kW]Range: Function:0.00 kW* [0.00 - 10000.00 kW] Displays motor power in kW. The value shown is calculated on the basis of the actual motor voltageand motor current. The value is filtered, and therefore approx. 30 ms may pass from when an inputvalue changes to when the data read-out values change. The resolution of read-out value on fieldbusis in 10 W steps.3 Parameter descriptions FC 300 Programming Guide212 MG.33.M8.02 - VLT® is a registered Danfoss trademark3