130BP079.10MenuStatus QuickSetupMainMenuP 2-03 Setup 1Illustration 2.242.1.16 Local Control KeysKeys for local control are found at the bottom of the LCP.130BP046.10Handon Off Autoon ResetIllustration 2.25[Hand On] enables control of the frequency converter viathe LCP. [Hand On] also starts the motor and it is nowpossible to enter the motor speed data by means of thearrow keys. The key can be selected as [1] Enable or [0]Disable via 0-40 [Hand on] Key on LCP.External stop signals activated by means of control signalsor a serial bus will override a 'start' command via the LCP.The following control signals are still active when [HandOn] is activated:• [Hand On] - [Off] - [Auto On]• Reset• Coasting stop inverse• Reversing• Set-up select lsb - Set-up select msb• Stop command from serial communication• Quick stop• DC brake[Off] stops the connected motor. The key can be selectedas [1] Enable or [0] Disable via 0-41 [Off] Key on LCP.If no external stop function is selected and the [Off] key isinactive the motor can be stopped by disconnecting thevoltage.[Auto On] enables the frequency converter to becontrolled via the control terminals and/or serial communi-cation. When a start signal is applied on the controlterminals and/or the bus, the frequency converter willstart. The key can be selected as [1] Enable or [0] Disablevia 0-42 [Auto on] Key on LCP.NOTEAn active HAND-OFF-AUTO signal via the digital inputs hashigher priority than the control keys [Hand On] [Auto On].[Reset] is used for resetting the frequency converter afteran alarm (trip). It can be selected as [1] Enable or [0]Disable via 0-43 [Reset] Key on LCP.2.1.17 Initialisation to Default SettingsInitialise the frequency converter to default settings in twoways.Recommended initialisation (via 14-22 Operation Mode)1. Select 14-22 Operation Mode2. Press [OK]3. Select “Initialisation”4. Press [OK]5. Cut off the mains supply and wait until thedisplay turns off.6. Reconnect the mains supply - the frequencyconverter is now reset.14-22 Operation Mode initialises all except:14-50 RFI Filter8-30 Protocol8-31 Address8-32 FC Port Baud Rate8-35 Minimum Response Delay8-36 Max Response Delay8-37 Max Inter-Char Delay15-00 Operating Hours to 15-05 Over Volt's15-20 Historic Log: Event to 15-22 Historic Log:Time15-30 Fault Log: Error Code to 15-32 Alarm Log:TimeHow to Programme VLT® AutomationDrive Programmming GuideMG33ME02 - VLT® is a registered Danfoss trademark 212 2