6 Application Examples6.1 IntroductionThe examples in this section are intended as a quickreference for common applications.• Parameter settings are the regional default valuesunless otherwise indicated (selected inparameter 0-03 Regional Settings).• Parameters associated with the terminals andtheir settings are shown next to the drawings.• Required switch settings for analog terminals A53or A54 are also shown.NOTICE!When using the optional STO feature, a jumper wire maybe required between terminal 12 (or 13) and terminal 37for the frequency converter to operate with factorydefault programming values.NOTICE!The following examples refer only to the frequencyconverter control card (right LCP), not the filter.6.2 Application ExamplesCAUTIONThermistors must use reinforced or double insulation tomeet PELV insulation requirements.ParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB929.10Function Settingparameter 1-29Automatic MotorAdaptation(AMA)[1] EnablecompleteAMAparameter 5-12Terminal 27Digital Input[2]* Coastinverse*=Default ValueNotes/comments: Parametergroup 1–2* Motor Data must beset according to motorTable 6.1 AMA with T27 ConnectedParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB930.10Function Settingparameter 1-29Automatic MotorAdaptation(AMA)[1] EnablecompleteAMAparameter 5-12Terminal 27Digital Input[0] Nooperation*=Default ValueNotes/comments: Parametergroup 1–2* Motor Data must beset according to motorTable 6.2 AMA without T27 ConnectedApplication Examples Installation ManualMG37A322 Danfoss A/S © Rev. 04/2015 All rights reserved. 616 6