1.2 Hand On/Auto On ModeAfter installation (see 3 Installation), there are two simpleways to start up the frequency converter, Hand On andAuto On mode. At the first power-up it is in auto on mode.130BD062.10D HandOn ResetAutoOnOKOnWarnAlarmIllustration 1.3 Location of Hand On, Off/Reset and Auto Onkeys on the NLCP• Press [Hand On] to provide a local start commandto the frequency converter. Press [▲] and [▼] toincrease and decrease speed.• Press [Off/Reset] to stop the frequency converter.• Press [Auto On] to control the frequencyconverter either via control terminals or serialcommunication.CAUTIONSince the frequency converter is in auto on mode at firstpower up, the frequency converter may start the motordirectly.NOTICE5-12 Terminal 27 Digital Input has coast inverse as defaultsetting. Connect terminals 12 and 27 to test Hand On/Auto On running.For LCP operation, see 4 User Interface and Programming.1.3 Application SelectionsUse the selections for quick application set-up of the mostcommon applications by setting 0-16 Application Selections.When necessary, the selections can be modified forindividual needs. All selections are for Auto On mode.NOTICEWhen an application is selected, relevant parameters areautomatically set. Customer specific configuration of allparameters based on specific requirements is stillpossible.CAUTIONIf any of the applications below are selected, relay 1 willbe set to [Running] and relay 2 will be set to [Alarm]ApplicationPumps, fans, compressors130BC430.10+24V 12DI1 18DI2 19DI3 27DI4 29DI5 32DI6 33DI7 31COM 20+10V 50AI1 53 - +AI2 54COM 55AO1 45AO2 42123456R1R2FC 360StartCoast inverseJog4-20mADescriptionFor applications where avalue (e.g. pressure,temperature) must bekept at a desired level bysensor feedbackParameter settings1-00 (Configuration Mode): [3] Process Close Loop1-03 (Torque Characteristics): [1] Variable Torque3-00 (Ref Range): [0] Min- Max3-15 (Ref Source 1): [0] No Function4-12 (Motor Low Limit): 30.0 Hz4-14 (Motor High Limit): 50.0 Hz5-10 (DI 18 Selection): [8] Start5-12 (DI 27 Selection): [2] Coast Inverse5-14 (DI 32 Selection): [14] Jog5-40 (Relay 1 Selection): Running5-40 (Relay 2 Selection): Alarm6-22 (AI 54 Low): 4.0 mA6-23 (AI 54 High): 20.0 mA6-29 (AI 54 Mode): [0] Current Mode6-70 (Term 45 Mode): [0] 0-20 mA6-71 (AO45): [100] Output freq6-90 (Term 42 Mode): [0] 0-20 mA6-91 (AO42): [103] Motor current7-20 (Process CL feedback source): [2] Analog input 54Table 1.3 [1] Process Closed LoopQuick Start VLT® AutomationDrive FC 360 Quick Guide4 MG06A302 - VLT® is a registered Danfoss trademark11