6.2 Parameters: 0-** Operation and Display6.2.1 0-0* Basic Settings0-01 LanguageOption: Function:Defines the language to be used in display.[0] * English[1] German[2] French[3] Danish[4] Spanish[5] Italian0-02 Motor Speed UnitOption: Function:Select display of motor speed parameters (i.e.references, feedbacks and limits) in terms of shaftspeed (RPM) or output frequency to the motor (Hz).[0] * RPM[1] HzNOTEThis parameter cannot be adjusted while the motor isrunning.0-04 Operating State at Power-up (Hand)Option: Function:Selects the operating mode uponreconnection of the frequency converter tomains voltage after power down in Hand(local) operation mode.[0] Resume Restarts the frequency converter, maintainingthe same and the same start/stop settings(applied by [Hand On/Off]) as before thefrequency converter was powered down.[1] * Forced stop,ref=oldRestarts the frequency converter with asaved local reference, after mains voltagereappears and after pressing [Hand On].[2] Forced stop,ref=0Resets the local reference to 0 uponrestarting the frequency converter.0-10 Active Set-upOption: Function:Select the set-up to control the frequencyconverter functions.[0] Factory setup Cannot be changed. It contains the Danfossdata set, and can be used as a data sourcewhen returning the other set-ups to aknown state.[1] * Set-up 1 [1] Set-up 1 to [4] Set-up 4 are the fourseparate parameter set-ups within which allparameters can be programmed.0-10 Active Set-upOption: Function:[2] Set-up 2[3] Set-up 3[4] Set-up 4[9] Multi Set-up Remote selection of set-ups using digitalinputs and the serial communication port.This set-up uses the settings from 0-12 ThisSet-up Linked to. Stop the frequencyconverter before making changes to open-and closed loop functionsUse 0-51 Set-up Copy to copy a set-up to one or all otherset-ups. Stop the frequency converter before switchingbetween set-ups where parameters marked ‘notchangeable during operation’ have different values. Toavoid conflicting settings of the same parameter withintwo different set-ups, link the set-ups together using0-12 This Set-up Linked to. Parameters which are ‘notchangeable during operation’ are marked FALSE in theparameter lists in 6.16 Parameter Lists.0-11 Edit Set-upOption: Function:Select the set-up to be edited (i.e.programmed) during operation; either theactive set-up or one of the inactive set-ups.[0] Factory setup Cannot be edited but it is useful as a datasource to return the other set-ups to aknown state.[1] * Set-up 1 [1] Set-up 1 to [4] Set-up 4 can be editedfreely during operation, independently ofthe active set-up.[2] Set-up 2[3] Set-up 3[4] Set-up 4[9] Active Set-up Can also be edited during operation. Editthe chosen set-up from a range of sources:LCP, FC RS-485, FC USB or up to five fieldbussites.Parameter Descriptions Operating Instructions VLT® CDS302 and CDS30346 MG34M302 - VLT® is a registered Danfoss trademark/Commercial Compressor66