3. How to Configure the System3.1. Configure the DeviceNet NetworkAll DeviceNet stations that are connected tothe same bus network must have a uniquestation address. The DeviceNet address of thefrequency converter can be selected via:- Hardware switches (default 63)- Parameter 10-02MAC ID (default63)- Class code 0X03, Instance 1, Attrib-ute 13.1.1. Setting the DeviceNet Address using the Hardware SwitchesSetting the DeviceNet Address using the Hardware Switches: Using the hardware switches it ispossible to select an address range from 0-63 (factory setting 63) according to the table below:Switch 8 7 6 5 4 3 2 1Address value - - +32 +16 +8 +4 +2 +1Ex. address 5 - - OFF OFF OFF ON OFF ONEx. address 20 - - OFF ON OFF ON OFF OFFEx. address 35 - - ON OFF OFF OFF ON ONNB!Switch off the power supply before changing the hardware switches.The address change will come into effect at the next power-up, and can be read in par. 10-02MAC ID.3.1.2. Setting the DeviceNet Address via Par. 10-02MAC IDThe address can be set via par. 10-02MAC ID if the hardware switches are set to 63 (factorysetting). The address change will come into effect at the next power-up.3.1.3. Setting the DeviceNet Address with the Object Class Code0x03, Attribute 1, Instance 1The address can be set via the DeviceNet object class code 0x03 attribute 1 command if thehardware switch is set to 63 (factory setting). A new address becomes effective immediately afterthe class code 0x03, Instance 1, Attribute 1 command.FC 100/ 200/ 300 DeviceNet 3. How to Configure the SystemMG.33.D3.02 - VLT® is a registered Danfoss trademark 193