SSymptom Possible cause Test SolutionMotor running in wrongdirectionMotor rotation limit Check that 4-10 Motor SpeedDirection is programmed correctly.Program correct settingsActive reversing signal Check if a reversing command isprogrammed for the terminal inparameter group 5-1* Digitalinputs..Deactivate reversing signalWrong motor phase connection See 2.4.5 Motor Rotation Check inthis manualMotor is not reachingmaximum speedFrequency limits set wrong Check output limits in 4-13 MotorSpeed High Limit [RPM], 4-14 MotorSpeed High Limit [Hz] and 4-19 MaxOutput Frequency.Program correct limitsReference input signal not scaledcorrectlyCheck reference input signalscaling in 6-0* Analog I/O Mode andparameter group 3-1* References.Reference limits in parametergroup 3-0* Reference Limit.Program correct settingsMotor speed unstablePossible incorrect parametersettingsCheck the settings of all motorparameters, including all motorcompensation settings. For closedloop operation, check PID settings.Check settings in parameter group1-6* Analog I/O mode. For closedloop operation, check settings inparameter group 20-0* Feedback..Motor runs roughPossible over-magnetization Check for incorrect motor settingsin all motor parametersCheck motor settings in parametergroups 1-2* Motor Data, 1-3* AdvMotor Data, and 1-5* Load Indep.Setting.Motor will not brakePossible incorrect settings in thebrake parameters. Possible tooshort ramp down timesCheck brake parameters. Checkramp time settingsCheck parameter group 2-0* DCBrake and 3-0* Reference Limits.Open power fuses or circuitbreaker tripPhase to phase short Motor or panel has a short phaseto phase. Check motor and panelphase for shortsEliminate any shorts detectedMotor overload Motor is overloaded for theapplicationPerform startup test and verifymotor current is within specifi-cations. If motor current isexceeding nameplate full loadcurrent, motor may run only withreduced load. Review the specifi-cations for the application.Loose connections Perform pre-startup check for looseconnectionsTighten loose connectionsMains current imbalancegreater than 3%Problem with mains power (SeeAlarm 4 Mains phase lossdescription)Rotate input power leads into thefrequency converter one position: Ato B, B to C, C to A.If imbalanced leg follows the wire,it is a power problem. Check mainspower supply.Problem with the frequencyconverterRotate input power leads into thefrequency converter one position: Ato B, B to C, C to A.If imbalance leg stays on sameinput terminal, it is a problem withthe unit. Contact the supplier.Motor current imbalancegreater than 3%Problem with motor or motorwiringRotate output motor leads oneposition: U to V, V to W, W to U.If imbalanced leg follows the wire,the problem is in the motor ormotor wiring. Check motor andmotor wiring.Problem with the frequencyconvertersRotate output motor leads oneposition: U to V, V to W, W to U.If imbalance leg stays on sameoutput terminal, it is a problemwith the unit. Contact the supplier.Basic Troubleshooting VLTp Refrigeration Drive Operating Instructions64 MG16J102 - VLTp is a registered Danfoss trademark99inverter.ru (812) 702-47-50