3.13 Main Menu - Data Readouts - Group 1616-00 Control WordRange: Function:0 * [0 - 65535 ] View the Control word sent from thefrequency converter via the serial communi-cation port in hex code.16-01 Reference [Unit]Range: Function:0 ReferenceFeed-backUnit*[-999999 - 999999ReferenceFeed-backUnit]View the presentreference value appliedon impulse or analogbasis in the unitresulting from theconfiguration selectedin 1-00 ConfigurationMode (Hz, Nm or RPM).16-02 Reference [%]Range: Function:0 %* [-200 - 200%]View the total reference. The totalreference is the sum of digital, analog,preset, bus, and freeze references, pluscatch-up and slow-down.16-03 Status WordRange: Function:0 * [0 - 65535 ] View the Status word sent from the frequencyconverter via the serial communication port inhex code.16-05 Main Actual Value [%]Range: Function:0 %* [-100 - 100 %] View the two-byte word sent with theStatus word to the bus Master reportingthe Main Actual Value.16-09 Custom ReadoutRange: Function:0 CustomRea-doutUnit*[-999999.99 -999999.99CustomRea-doutUnit]View the user-definedreadouts as defined in0-30 Custom Readout Unit,0-31 Custom Readout MinValue and 0-32 CustomReadout Max Value.3.13.1 16-1* Motor Status16-10 Power [kW]Range: Function:0 kW* [0 -1000 kW]Displays motor power in kW. The value shownis calculated on the basis of the actual motorvoltage and motor current. The value is16-10 Power [kW]Range: Function:filtered, and therefore approx. 30 ms may passfrom when an input value changes to whenthe data read-out values change. Theresolution of read-out value on fieldbus is in10 W steps.16-11 Power [hp]Range: Function:0 hp* [0 - 1000hp]View the motor power in HP. The value shownis calculated on the basis of the actual motorvoltage and motor current. The value isfiltered, and therefore approximately 30 msmay pass from when an input value changesto when the data read-out values change.16-12 Motor VoltageRange: Function:0 V* [0 - 6000 V] View the motor voltage, a calculated valueused for controlling the motor.16-13 FrequencyRange: Function:0 Hz* [0 - 6500 Hz] View the motor frequency, withoutresonance dampening.16-14 Motor currentRange: Function:0 A* [0 - 1856A]View the motor current measured as a meanvalue, IRMS. The value is filtered, and thusapproximately 30 ms may pass from when aninput value changes to when the data read-out values change.16-15 Frequency [%]Range: Function:0 %* [-100 -100 %]View a two-byte word reporting the actualmotor frequency (without resonancedampening) as a percentage (scale 0000-4000Hex) of 4-19 Max Output Frequency. Set9-16 PCD Read Configuration index 1 to send itwith the Status Word instead of the MAV.Parameter Description VLT® Refrigeration Drive Programming Guide104 MG16H102 - VLT® is a registered Danfoss trademark33