VLT ® FCD Series■ Technical functions600-605 Operating DataValue:Par. no. Description Display text Unit Range600 Operating hours (OPERATING HOURS) Hours 0-130,000.0601 Hours run (RUNNING HOURS) Hours 0-130,000.0602 kWh counter (KWH COUNTER) kWh Depends on unit603 Number of power-up’s (POWER UP’S) Number of times 0-9999604 Number of overtemperatures (OVER TEMP’S) Number of times 0-9999605 Number of overvoltages (OVER VOLT’S) Number of times 0-9999Function:These parameters can be read out via the serialcommunication port and the LCP control unit.Description of choice:Parameter 600, Operating hours:Gives the number of hours the frequencyconverter has been operating. The value issaved every hour and when there is a mainsfailure. This value cannot be reset.Parameter 601, Hours run:Gives the number of hours the motor has beenoperating since the reset in parameter 619 Resetof hours-run counter. The value is saved everyhour and when there is a mains failure.Parameter 602, kWh counter:Gives the frequency converter’s output energy inkWh. The calculation is based on the mean kWvalue over one hour. This value can be reset usingparameter 618 Reset of kWh counter.Range: 0 - depends on unit.Parameter 603, Number of power-ups:Gives the number of power-ups of the supply voltageundertaken on the frequency converter.Parameter 604, Number of overtemperatures:Gives the number of overtemperature faults that havebeen registered on the frequency converter’s heat sink.Parameter 605, Number of overvoltages:Gives the number of overvoltages of the intermediatecircuit voltage in the frequency converter. This is onlycounted when Alarm 7 Overvoltage is active.NB!:Parameters 615-617 Fault log cannot be readout via the integral control unit.615 Fault log: Error code(F.LOG: ERROR COD)Value:[Index 1 - 10] Error code: 0 - 99Function:In this parameter it is possible to see the reason fora trip (cut-out of the frequency converter) occurring.10 [1-10] log values are defined.The lowest log number [1] contains the latest/mostrecently saved data value. The highest log number[10] contains the oldest data value saved. If a tripoccurs, it is possible to see the cause, time and apossible value of the output current or output voltage.Description of choice:Given as a fault code, in which the number refers to atable. See the table in Warnings/alarm messages.616 Fault log: Time(F.LOG: TIME)Value:[Index 1 - 10] Hours: 0 - 130,000.0Function:In this parameter it is possible to see the total numberof operating hours in connection with the last 10 trips.10 [1-10] log values are denoted. The lowestlog number [1] contains the latest/most recentlysaved data value, and the highest log number[10] contains the oldest data value.Description of choice:Read out as one value.✭ = factory setting. () = display text [] = value for use in communication via serial communication portMG.04.B7.02 - VLT is a registered Danfoss trademark96