16-11 Power [hp]Range: Function:0 hp* [0 - 1000 hp] View the DC link power in hp. The valueshown is calculated on the basis of theactual motor voltage and motor current.16-12 Motor VoltageRange: Function:0 V* [0 - 65535 V] View the motor voltage, a calculated valueused for controlling the motor.16-13 FrequencyRange: Function:0 Hz* [0 - 6553.5 Hz] View the motor frequency, withoutresonance dampening.16-14 Motor currentRange: Function:0 A* [0 - 655.35 A] View the motor current measured as amean value, IRMS.16-15 Frequency [%]Range: Function:0 %* [0 - 6553.5 %]16-18 Motor ThermalRange: Function:0 %* [0 - 100 %]3.12.3 16-3* Drive Status16-30 DC Link VoltageRange: Function:0 V* [0 - 65535 V] View a measured value.16-34 Heatsink Temp.Range: Function:0 °C* [0 - 255 °C]16-35 Inverter ThermalRange: Function:0 %* [0 - 255 %]16-36 Inv. Nom. CurrentRange: Function:0 A* [0 - 655.35 A] View the inverter nominal current, whichshould match the nameplate data on theconnected motor. The data are used formotor protection, etc.16-37 Inv. Max. CurrentRange: Function:0 A* [0 - 655.35 A] View the inverter maximum current. Thedata are used for calculation of adjustablefrequency drive protection, etc.16-38 SL Controller StateRange: Function:0 * [0 - 20 ] View the actual state of the Smart LogicController (SLC).3.12.4 16-5* Ref. & Feedb.16-50 External ReferenceRange: Function:0 %* [-200 - 200 %]16-52 Feedback[Unit]Range: Function:0 ProcessCtrlUnit* [-4999 - 4999ProcessCtrlUnit]View the feedbackresulting from theselection of scaling in3-02 Minimum Referenceand 3-03 MaximumReference.3.12.5 16-6* Inputs and Outputs16-60 Digital InputRange: Function:0 * [0 - 65535 ] View actual state of the digital inputs 18, 19,27 and 29.Bits definitionBit 0 UnusedBit 1 UnusedBit 2 Digital input term. 29Bit 3 Digital input term. 27Bit 4 Digital input term. 19Bit 5 Digital input term. 18Bit 6~15 UnusedTable 3.1016-61 Terminal 53 SettingOption: Function:View the setting of input terminal 53. Current= 0; Voltage = 1.[0] Current mode[1] Voltage modeParameters VLT® HVAC Basic Drive Programming GuideMG18B222 - VLT® is a registered Danfoss trademark 3-553 3