1.7 General Specifications1.7.1 Mains Supply 3 x 200-240 V ACfrequency converter PK25PK37PK75P1K5P2K2 P3K7P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45KTypical shaft output (kW) 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0Typical shaft output (hp) 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0IP20 frame H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8Max. cable size in terminals (mains,motor) [mm2/AWG]4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 35/2 35/2 50/1 50/1 95/0 120/(4/0)Output currentRELAY 2130BB632.1040°C ambient temperatureContinuous(3 x 200-240 V)[A]1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0Intermittent(3 x 200-240 V)[A]1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0Max. input currentRELAY 2130BB633.10Continuous(3 x 200-240 V)[A]1.1 1.6 2.8 5.6 8.6/7.214.1/12.021.0/18.028.3/24.041.0/38.252.7 65.0 76.0 103.7 127.9 153.0Intermittent(3 x 200-240 V)[A]1.2 1.8 3.1 6.2 9.5/7.915.5/13.223.1/19.831.1/26.445.1/42.058.0 71.5 83.7 114.1 140.7 168.3Max. mains fuses See 1.3.6 FusesEstimated powerloss [W], Bestcase/typical1)12/1415/1821/2648/6080/10297/120182/204229/268369/386512 658 804 1015 1459 1350Weight enclosureIP20 [kg]2. 2.0 2.0 2.1 3.4 4.5 7.9 7.9 9.5 24.5 24.5 36.0 36.0 51.0 51.0Efficiency [%],Best case/Typical197.0/96.597.3/96.898.0/97.697.6/97.097.1/96.397.9/97.497.3/97.098.5/97.197.2/97.197.0 96.9 96.8 97.0 96.5 97.3Output current50°C ambient temperatureContinuous (3 x200-240 V) [A]1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0 33.0 53.5 66.6 79.2 103.5 128.7 153.0Intermittent (3 x200-240 V) [A]1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3 36.3 58.9 73.3 87.1 113.9 141.6 168.31) At rated load conditionsQuick Guide VLT HVAC Basic Drive Quick GuideMG18A302 - VLT® is a registered Danfoss trademark 351 1