3.6.14. FusesBranch circuit protectionIn order to protect the installation against electrical and fire hazard, all branch circuits in an in-stallation, switch gear, machines etc., must be short-circuited and over-current protected accord-ing to national/international regulations.Short-circuit protectionThe frequency converter must be protected against short-circuit to avoid electrical or fire hazard.Danfoss recommends using the fuses mentioned below to protect service personnel and equip-ment in case of an internal failure in the drive. The frequency converter provides full short-circuitprotection in case of a short-circuit on the motor output.Over-current protectionProvide overload protection to avoid fire hazard due to overheating of the cables in the installation.The frequency converter is equipped with an internal over-current protection that can be used forupstream overload protection (UL-applications excluded), see par. 4-18. Moreover, fuses or circuitbreakers can be used to provide the over-current protection in the installation. Over-current pro-tection must always be carried out according to national regulations.Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000Arms (symmetrical).Fuse TablesSize/TypeBuss-mannE1958JFHR2**Buss-mannE4273T/JDDZ**SIBAE180276RKI/JDDZLittelFuseE71611JFHR2**Ferraz-ShawmutE60314JFHR2**Buss-mannE4274H/JDDZ**BussmannE125085JFHR2*InternalOptionBussmannP110 FWH-300JJS-3002028220-315L50S-300 A50-P300 NOS-300170M3017 170M3018P132 FWH-350JJS-3502028220-315L50S-350 A50-P350 NOS-350170M3018 170M4016P160 FWH-400JJS-400206xx32-400L50S-400 A50-P400 NOS-400170M4012 170M4016P200 FWH-500JJS-500206xx32-500L50S-500 A50-P500 NOS-500170M4014 170M4016P250 FWH-600JJS-600206xx32-600L50S-600 A50-P600 NOS-600170M4016 170M4016Table 3.5: D enclosures, 380-480 V*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be substituted for external use**Any minimum 480 V UL listed fuse with associated current rating may be used to meet ULrequirements.Size/TypeBussmannE125085JFHR2AmpsSIBAE180276JFHR2Ferraz-ShawmutE76491JFHR2P110 170M3017 315 2061032.315 6.6URD30D08A0315P132 170M3018 350 2061032.350 6.6URD30D08A0350P160 170M4011 350 2061032.350 6.6URD30D08A0350P200 170M4012 400 2061032.400 6.6URD30D08A0400P250 170M4014 500 2061032.500 6.6URD30D08A0500P315 170M5011 550 2062032.550 6.6URD32D08A0550Table 3.6: D enclosures, 525-600 V3. How to InstallVLT® HVAC DRIVE High PowerOperating Instruction54 MG.11.F1.02 - VLT® is a registered Danfoss trademark3