1.3.3 Mechanical DimensionsAabBC D130BB614.10efade130BC205.10efae130BC246.10Table 1.5Power Height [mm/inch] Width [mm/inch] Depth [mm/inch]Hole [mm]Frame IP class 3x380-480 V A A incl.decouplingplateA B b C DH1 IP20 0.37-1.5 kW/0.5-2 hp195/7.7 273/10.7 183/7.2 75/3 56/2.2 168/6.6 4.5H2 IP20 2.2-4 kW/3-5.4 hp227/8.4 303/11.9 212/8.3 90/3.5 65/2.6 190/7.5 5.5H3 IP20 5.5-7.5 kW/7.5-10 hp255/10 329/13 240/9.4 100/3.9 74/2.9 206/8.1 5.5H4 IP20 11-15 kW/15-20 hp296/11.7 359/14.1 275/10.8 135/5.3 105/4.1 241/9.5 7H5 IP20 18.5-22 kW/25-30 hp334/13.1 402/15.8 314/12.4 150/5.9 120/4.7 255/10 7H6 IP20 30-45 kW/40-60 hp518/20.4 595/23.4635/25495/19.5 239/31.5 200/7.9 242/9.5 8.5H7 IP20 55-75 kW/100-120 hp550/21.7 630/24.8690/27.2521/20.5 313/12.3 270/10.6 335/13.2 8.5H8 IP20 90 kW/120 hp660/26 800/31.5 631/24.8 375/14.8 330/13 335/13.2 8.5Table 1.6 Mechanical DimensionsThe dimensions are only for the physical units, but wheninstalling in an application it is necessary to add space forfree air passage both above and below the units. Theamount of space for free air passage is listed in Table 1.7:Enclosure Clearance needed for free air passage [mm]Frame IP class Above unit Below unitH1 20 100 100H2 20 100 100H3 20 100 100H4 20 100 100H5 20 100 100H6 20 200 200H7 20 200 200H8 20 225 225Table 1.7 Clearance Needed for Free Air PassageQuick Guide VLT® HVAC Basic Drive Cascade Controller Quick GuideMG18F402 - VLT® is a registered Danfoss trademark 51 1