102 Dell EMC Connectrix EC-1700 Cabinet Installation and Setup ManualInstalling Directors into the EC-1700 CabinetIMPORTANTDo NOT remove the factory baffle installed at U19-U22. Leave thebaffle in place. Install the MDS-92CAB-KIT on the outside of thevertical mounting rails. The baffle will be on the inside of themounting rails. You will need to temporarily loosen and/orunscrew the cable tray at the front of the cabinet and the largebaffles at the rear of the cabinet in order to gain access to themounting points for the MDS-92CAB-KIT slider rails and theU19-U22 baffle.Install the 9506 onto the MDS-92CAB-KIT mounting rails at U23 perthe Cisco installation instructions.IMPORTANTBe sure to use at least 6 clip nuts and screws on each side of themounting flanges of the 9506. Do NOT remove theMDS-92CAB-KIT once the 9506 has been installed and securedwithin the cabinet.As shown in Figure 71 on page 98 and Figure 72 on page 99,additional baffles from the MDS-BAFL-KIT will need to be installedabove the 9506. The number and type of baffle to be installed isdependent upon what, if any, other equipment is to be installed in thecabinet with the 9506.Installing additional bafflesThe baffles contained in the MDS-BAFL-KIT come in several sizes.The different sizes are used singly or in combination depending uponthe product mix within the cabinet. The examples shown in Figure 71on page 98 and Figure 72 on page 99 show the different combinationsof products and optional baffles, depicted in blue.IMPORTANTInstall the rubber gasketing strips on the optional baffles beinginstalled to minimize hot air leakage into the main cabinet cavity.