eZV-440 Version 2.1 Application Guide Page 42 of 67Document Edition 2.5Setpoints TabUse the Setpoints tab to enter your VAV and VVT system controls and setpoints. This sectiondescribes each field and its role in the VAV and VVT control system.For a list of setpoint configuration objects and the default values, go toAppendix A on page 58.For a description of the different modes of operation, go toSequence of Operations on page 47.You can change the temperature units in Global Settings on the General tab.Space Temperature SetpointsName of field DescriptionOccHeatingSetpoint Occupied Heating Setpoint: When the controller is in occupied mode,heating is turned on when the space temperature drops below this setpoint.UnOccHeatingSetpoint Unoccupied Heating Setpoint: When the controller is in unoccupied mode,heating is turned on when the space temperature drops below this setpoint.OccCoolingSetpoint Occupied Cooling Setpoint: When the controller is in unoccupied mode,cooling is turned on when the space temperature rises above this setpoint.UnOccCoolingSetpoint Unoccupied Cooling Setpoint: When the controller is in unoccupied mode,cooling is turned on when the space temperature rises above this setpoint.