108661For more information, visit www.desatech.comFor more information, visit www.desatech.com10Vertical (V) Horizontal (H)T32 Series 31" min. 17" max.T36 Series 35" min. 17" max.Horizontal HighWind SquareTerminationWall Firestop45° ElbowGROUND FLOOR INSTALLATIONRecommended Applications:• Installation using cabinet surrounds• Through the wall using round or square termination (up to 12"horizontal pipe)• NOT FOR CORNER INSTALLATIONVENTING INSTALLATIONINSTRUCTIONSContinuedVENTING INSTALLATION INSTRUCTIONSInstallation Planning (Cont.)AdjustablePipe 12" Max.Horizontal Termination ConfigurationsFigures 14 through 18 show different configurations and alternativesfor venting with horizontal termination. Each figure includes a chartwith critical minimum and maximum dimensions which MUST bemet.IMPORTANT: Remember that a horizontal run of venting musthave a 1/4" rise for every 12" of run toward the termination.Figure 13 - Typical Horizontal Termination Cap Mounting withAdditional Siding Standoff InstalledSiding StandoffScrewsHigh WindTerminationApply Mastic toOutside Edge ofStandoffExterior Wallwith Vinyl Siding10" x 10"FramedOpeningMaintain 1"Minimum AirSpace AroundOuter Pipe WhenPenetrating a WallMinimum PipeOverlap 11 /4 "WallFirestopDirect VentPipeWARNING: Never run vent downward as this maycause excessive temperatures which could cause afire. Operation of improperly installed and main-tained venting system could result in serious injury,property damage or loss of life.Square TerminationFigure 14 - Horizontal Termination Configuration for Square andRound Terminations45° ElbowWallFirestopRoundTerminationCapExterior Portion of WallFirestop (RoundTermination Only)Round Termination(Kit HTK Shown)Slide RingOver Elbow toCompleteConnection