Product Manual Rosa ThermostatEAE KNX Rosa Thermostat Rosa Thermostat PM R1.0©EAE Technology www.eaetechnology.com Page53 / 774.4.4.3.1 ParametersParameter Setting DescriptionControl Value Normal / Inverse Invert the output of the controller. For example, ifnormal output is 1, then inverted output is 0.Cyclic Sending Interval 1…5…255 Time period to send heating control value over“Heating Control Value” communication object.Hysteresis (1/10 K) 1…10…255 Hysteresis value (Chapter 4.4.3.1.3)Spot Heat Protection checked / uncheckedThis parameter enables the Heat Protection viausing Spot Temperature Sensor. Spot Temperaturesensor must be enabled in "Temperature Sensor"page to show this parameter.Table 334.4.4.3.2 Communication ObjectsNo Object Name Function Data Type Flags61 Heat Control Value Send1 bitCTDPT 1.002Heating actuator will be controlled through this communication object.Table 344.4.4.4 Fan CoilFigure 17Heating control parameters for fan coil controller type should be configured here. For more informationabout on/off controller read Chapter 4.4.3.1.4.