114.3 Intelligent card (optional)There is an intelligent slot on the rear panel of the UPS, it’s for SNMP card and drycontacts. Users can insert any type intelligent card from those three into it to monitorand manage the UPS. And users don’t have to turn off the UPS when install theintelligent card. Follow below process: First of all, remove the intelligent slot cover; Then insert the intelligent card (SNMP card and dry contacts); Finally, screw the intelligent card back.> SNMP card (optional)SNMP card on UPS is compatible with the most software, hardware and networkoperating system, it is a network management of UPS, with this function, UPS canlogin on internet , which can supply information of UPS status and input power, andeven possible to control UPS via net management system.SNMP interface is set as below: Bit rate: 2400bps> Dry contacts card (optional)Insert the dry contacts card into the intelligent slot. It’s another type function ofintelligent monitoring.Position DefinitionPIN1 ON:UPS is malfunctioningPIN2 ON:Alarm(system failure)PIN3 GroundPIN4 Remote shutdownPIN5 CommonPIN6 ON:Bypass modePIN7 ON:Battery lowPIN8 ON:Inverter mode;OFF:Bypass modePIN9 ON:No AC power in