3Instruction Leaflet IL2C13761H11Effective March 2020Installation instructions for KirkKey Interlock Kit (2C12891G21) inMagnum low-voltage circuit breakersEATON www.eaton.comSection 2: Installation of key locksProceed with the following 14 steps:IMPORTANTDO NOT REINSERT KEY UNTIL STEP 6.Step 1: First remove key from key lock (A). Then remove twoscrews from back of key lock and discard the cam arm and screws.Remove one knurled nut from barrel of lock.Cam arm (to beremoved)Knurled nutFigure 2. Step 1Step 2: Remove second knurled nut from key lock body and placebushing (B) on cylinder body. Note orientation of key lock, and thenmount to lock mounting plate (C) with the knurled nut.IMPORTANTDO NOT INSERT KEY.Key lock (A)Bushing (B)Knurled nutKirk lock mountingplate (C)Figure 3. Step 2Step 3: Put torsion spring (D) on guide pin (E). Note the orientationof spring legs, and carefully press the knurled end of guide pin intohole in key lock body to the depth of the knurl. This step requires anArbor press, vise, or equivalent.IMPORTANTDO NOT INSERT KEY.Key lockTorsionspring (D)Guide pin (E)Figure 4. Step 3Step 4. Mount cylinder interlock adapter (F) to hexagonal standoff(G) with 1/2 inch long cap head screw (H) and tighten securely.Attach cable assembly (I) to other end of hexagonal standoff withshoulder screw (J).IMPORTANTDO NOT INSERT KEY.Hex standoff(G)Cable assembly(I)Cap screw(H)Cylinder interlockadapter (F)Shoulderscrew (J)Figure 5. Step 4