-55-Appendix 1Model 3C3 20kVA EX 3C3 30kVA EX 3C3 40kVA EXPower Rating 20kVA/16kW 30kVA/24kW 40kVA/32kWConnection 3-Phase 3-Wires or 3-Phase +N (Per customer's requirement)Frequency 56~64HzPower factor ≥0.99Voltage rating Voltage rating (+25% / -45%)VAC(when input voltage<75% outputpower derating is required)InputBypass Voltage range Voltage rating±15%Connection 3-Phase +N+GVoltage rating 380/220 or (Per customer's requirement)Power factor 0.8Frequency tolerance 60Hz±4Hz(track bypass frequency input ;when input frequency exceeds±4Hz or under the mode of battery power supply, frequency outputshould be±0.1%of nominal)Overload capability 110% 60min. Auto-jump bypass111%< Load≤125% 10min. Auto-jump bypass125%< load≤150% 1min. Auto-jump bypassOutputUnbalanced load capability 100%Ambient temperature 0-40℃Storage temperature –25-55℃Ambient humidity 10-90 % (non-condensing)OperatingEnvironmentAltitude ≤1000m14 Pcs ±168VDC/±189VDC15 Pcs ±180VDC/±202.5VDCNominal batteryvoltage/Ratedcharging voltage 16 Pcs ±192VDC/±216VDCN.W/Contain transformer 119/181/224/286Kg 164/235/305/376Kg 171/261/336/426KgWeight G.W/Contain transformer 121/183/226/288Kg 167/238/308/379Kg 174/264/339/429KgUPS Dimension(W*D*H)(mm) 420*800*1100 520*885*1320 520*885*1320Safety Standard National Standard BSMIESD IEC61000-4-2 Level 4RS IEC61000-4-3 Level 3EFT IEC61000-4-4 Level 4EMSSURGE IEC61000-4-5 Level 4EMI Radiation and Conduction CNS14757-2WARNING: This is a product for commercial and industrial application in the second environment-installationrestrictions or additional measures may be needed to prevent disturbances.