DSD-5P2208 19••••5.7 UPS remote control functionsConnectivity cardsConnectivity cards allow the UPS to communicate in a variety of networking environments and with different types ofdevices. The 5P Gen2 models have one available communication bay for the following connectivity cards:Gigabit Network card (Network-M2, Network-M3) : provides a Gigabit Ethernet connection and enables secure UPSmonitoring over HTTPS web browser interface, SNMP v1/v3 protocol and email alarms. In addition, up to 3Environmental Monitoring Probes can be attached to obtain humidity, temperature, smoke alarm, and securityinformation.Industrial Gateway card (INDGW-M2) : Provides Modbus RTU and Modbus TCP communication support in additionto the same secure UPS monitoring, management and sensor capability as the Gigabit Network card.Relay-MS card : provides isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPSalarm/OK, or on Bypass.INDRELAY-MS : The Industrial relay Card-MS (INDRELAY-MS) provides a simple way to remotely input UPS informationto an alarm system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and oneisolated dry contact input.Remote control connection and testCheck that the UPS is OFF and disconnected from the AC input source.Remove connector (4) after unscrewing the screws.Connect a normally closed volt-free contact (60 V DC / 30 V AC max., 20 mA max., 0.75 mm2 cable cross-section) betweenthe two pins of connector (4) (see diagram).Warning. This connector must only be connected to SELV (Safety Extra-Low Voltage) circuits.Contact open: UPS shutdownContact closed: UPS start-up (UPS connected to ACpower and AC power is available)Note. The local ON/OFF control using buttonoverrides the remote-control function.