Effective May 2010 2C14990H0205/10 AWA1230-2460Vertical adapters 800/1600A on fixedIZM low voltage circuit breakers warning(1) Only qualified electrical persOnnel shOuldbe permitted tO wOrk On the equipment.(2) always de-energize primary andsecOndary circuits if a circuit breakercannOt be remOved tO a safe wOrk lOcatiOn.(3) all circuit breakers shOuld be switchedtO the Off pOsitiOn and mechanism springsdischarged.failure tO fOllOw these steps fOr allprOcedures described in this instructiOnleaflet cOuld result in death, bOdily injury,Or prOperty damage. warningthe instructiOns cOntained in this awa and OnprOduct labels have tO be fOllOwed. Observethe five safety rules:– discOnnecting– ensure that devices cannOt beaccidentally restarted– verify isOlatiOn frOm the supply– earthing and shOrt-circuiting– cOvering Or prOviding barriers tOadjacent live partsdiscOnnect the equipment frOm the supply.use Only authOrized spare parts in the repairOf the equipment. the specified maintenanceintervals as well as the instructiOns fOrrepair and exchange must be strictly adheredtO prevent injury tO persOnnel and damage tOthe switchbOard.Section 1: General informationThe vertical adapter bolts directly to the rearprimary terminal pads. This adapter willnot accommodate cable adapters, only busconnections. A three-pole breaker will use a setof six adapters (eight for four-pole). All requiredmounting hardware is provided. Torque all boltsto 37–43 ft-lbs (50–58 Nm).Section 2: Installation ofvertical adaptersTo install the vertical adapters, proceed with thefollowing two steps:Step 1: Assemble as shown with the hardwareprovided. Assembly to a load conductor isdemonstrated.Figure 1. Step 1LoadConductor M10 x 45Hex BoltConical SpringWasherFlat WasherVertical AdapterFlat WasherM10 Hex Nut