223.3.3 EBM Wiring ConnectionIt is possible to connect more than one EBM in order to achieve any levelof autonomy without mains power. Connect any Battery Boxes in acascade as shown in the figure below:1. CONNECTION: Use 3 cables with 10 mm2 section (Earth, +, N and -)2. Connect the wires to the relative terminals, following exactly theinstructions given below:For 9E6Ki, 9E10Ki, 9E10KiXLa - Make sure that the fuse holder of the external battery box is open.b - Connect the earth (PE) wire to EBM’s earth (PE) screwc - Connect the positive (+) branch wire to EBM’s positive (+) terminal.d - Connect the negative (-) branch wire to EBM’s negative (-) terminal.The suggested tighten force is 1.6Nm. (Detailed wiring diagram see fig3-9~10)Fig.3-8 EBM terminal view (Fuse for 9E6Ki,9E10Ki, 9E10KiXLwithout Neutral)