Page 155-6kVA US_ENENGLISH2. PresentationSubmenu Available settings Default settingsIn/Out settingsInterrupt time If Bypass transfer is enabled,Interrupt time: [10ms] [20ms]Define break duration when transferon Bypass[10ms]Overloadprealarm[10%] … [102%]Load % when overload alarm occurs[102%]Redundancymode[Unitary UPS] [Hot Standby]Force slew rate value to 0.5Hz/sUnitary UPSOn/Off settingsCold start [Enabled] [Disabled]Authorize the product to start onbattery power.[Enabled]Forced reboot [Enabled] [Disabled]If mains recover during a shutdownsequence:If set to Enabled, shutdown sequencewill complete and wait 10 secondsprior to restart,If set to Disabled, shutdownsequence will not complete andrestart will occur immediately.[Enabled]Auto restart [Enabled] [Disabled]Authorize the product to restartautomatically when mains recoversafter a complete battery discharge.[Enabled]Auto start [Enabled] [Disabled]The UPS automatically starts up assoon as mains power is available(no need topress the button).[Disabled]Energy saving [Disabled] [100W] … [1000W]If Enabled, UPS will shutdown after5 min. of back-up time, if load is lessthan threshold.[Disabled]Sleep mode [Enabled] [Disabled]If Disabled, LCD and communicationwill turn OFF immediately after UPSis OFF.If Enabled, LCD and communicationstays ON 1h30 min after UPS is OFF.[Enabled]Remote command [Enabled] [Disabled]If Enabled, shutdown or restartcommands from software areauthorized.[Enabled]Bypass standby [Enabled] [Disabled]Define if output is powered fromBypass in Standby mode.[Disabled]Battery settingsAutomatic batterytestIn constant charge mode:[No test] [Every day] [Every week][Every month]In ABM cycling mode :[No test] [Every ABM cycle][Every ABM cycle]Low batterywarning[0%] ... [100%]The alarm triggers when the setpercentage of battery capacity isreached during back-up time.[20%]Restart bat. level [0%] ... [100%]If set, automatic restart will occuronly when percentage of batterycharge is reached.[0%]Battery chargemode[ABM cycling] [Constant charge] [ABM cycling]External battery [Auto detection][Manual EBM set.][Manual battery set.][No battery][Auto detection]Using standard EBM, UPSdetects automatically thenumber of EBM connectedDeep Disch.protect.[Yes] [No]If set to Yes, the UPS automaticallyprevents battery from deep dischargeby adapting end of back-up timevoltage threshold.Warranty void if set to No.[Yes]