A. THREE PHASE MOTORS-D.O.L. STARTER. LOCAL 3-WIRE (PUSH BUTTON) CONTROL.B. SINGLE PHASE MOTORS-D.O.L. STARTER LOCAL 3-WIRE (PUSH BUTTON) CONTROL.Connect supply to 1 and 5. Connect Motor to 4 and 6and insert a cable of cross-sectional area equal tothe supply cables between 3 and 2 as shown.NOTES TO STARTER DIAGRAMSCIRCUIT DIAGRAMSSUPPLYCONNECTCABLEMOTORMOTORSUPPLY1314L11 3 542 6Y96 9795STARTSTARTN LZXZX1496 979513STOPOSTOPO42 631 5YA2A1981718L2 L3A1A298L1 L2 L3 1718COIL PHASE TO NEUTRAL:- remove connector Y, connect Neutral to A1SEPARATE COIL SUPPLY:- remove connectors Y and Z, connect coil supply to A1 and 96.COIL VOLTAGE:- Ensure correct voltage coil is fitted for separate coil supply and phase toneutral applications.EXTERNAL INTERLOCK:- Remove connection Z and insert interlock between 5 and 96.ALARM CIRCUIT:- At trip an alarm signal voltage equal to the coil voltage is available between 98 and A1 when a link is addedbetween 96 & 97. The switch is rated at 440VA, 500V maximum.CONTROL CIRCUIT FUSES (10A MAX).Coil connected Phase to neutral (1 fuse):- remove connector Z and connect fuse between 5 and 96.Coil Connected Phase to Phase (2 fuses):- remove connector Z and connect fuse between 5 and 96. Remove connector Yand connect fuse between 1 and A1.NOTE:- the voltage rating of the fuse(s) must be suitable for the control circuit voltage.SHORT CIRCUIT PROTECTION:- Maximum sizes of fuses or MCB’s to give short-circuit protection to this starter are tabulatedon page 1.TO REVERSE DIRECTION OF ROTATION (3-Phase Motors):-Interchange any two supply lines 1, 3 or 5.REMOTE START/INCH/STOPCONTROLConnect as above except removelead X and add connections shown.REMOTEPUSHBUTTONSSTARTSTOPINCH17 18 A2LOCAL & REMOTE 3-WIRE(PUSH-BUTTON) CONTROLConnect as above except removelead X and add connections shown.REMOTEPUSHBUTTONSSTARTSTOP17 18 A2N L