System ControllerCopyright © 2018 Eaton Corporation. All Rights Reserved.IPN 997-00012-10A2 July 2018 45Generic System TypesIf the user does not have a suitable configuration file for a new SC300, or he/she needs to changethe operating voltage of a system, then the Generic System Types may be used as a startingpoint.To select a Generic System Type, in web go to Identity > Software and select an appropriate type.Suitable settings are then loaded into the SC300.• Master Configuration takes settings back to the last configuration loaded by web or DCTools.This is useful where settings have been incorrectly changed.• Factory wipes settings and resets to the normal ex-factory settings.• APS48V / APS24V / EPS48V LVD and EPS48V only load settings that are specific to that voltage orsystem type. Other settings are left unchanged.The settings loaded using Generic System Type may not be suitable for all systems.Where possible, obtain the appropriate configuration file.After selecting a Generic System Type, check system operation.If the original configuration is corrupt or unknown, this procedure should befollowed:1. Load the Factory configuration2. Load the appropriate Generic system type.These are the currently available Generic System Types:Generic System Type ActionUnknown No effect; does not change settings.Factory Loads the standard factory settings, except that IP addressesare not changed.Master Config Re-loads the last configuration file loaded by DCTools or weband saved by the SC300.APS48V Loads standard 48V positive earth settings.Set for 1 LVD only.APS24V Loads standard 24V negative earth settingsSet for 1 LVD only.EPS 48V LVD Loads a standard 48V positive earth settings.Includes an LVD.EPS48V Loads a standard 48V positive earth settings.No LVD.