608.2. Tests and environmental conditionsDisturbance testsTest Standard & Test class / level Test valueEmission EN 61000-6-4- Conducted EN 55011, class A 0.01 - 30 MHz- Emitted EN 55011, class A 30 - 1 000 MHzImmunity EN 61000-6-2 / IEC 60255-26- 1MHz damped IEC 60255-22-1 ±2.5kVp CM, ±1kVp DMoscillatory wave- Static EN 61000-4-2 class IV / 8 kV contact, 15 kV airdischarge (ESD) IEC 60255-22-2- Fast transients EN 61000-4-4 class IV / ±4 kV, 5/50 ns, 5 kHz(EFT) IEC 60255-22-4 class A- Surge EN 61000-4-5 class III / 2 kV, 1.2/50 μs, CMIEC 60255-22-51 kV, 1.2/50 μs, DM- Conducted EN 61000-4-6 class III / 0.15 - 80 MHz, 10 VemfHF field IEC 60255-22-6- Emitted EN 61000-4-3 class III / 80 - 2700 MHz, 10 V/mHF field IEC 60255-22-3- Voltage EN 61000-4-29 / 30%/1s, 60%/0.1s, 100%/0.05sinterruptions IEC 60255-11- Voltage EN 61000-4-17 / IEC 60255-11 12% of operating voltage (DC) / 10minalternativecomponent- Voltage dips EN 61000-4-11 30%/10ms, 100%/10msand short 60%/100msinterruptions >95%/5000ms- Power- EN 61000-4-8 300A/m (continuous), 1000A/m / 1-3sfrequencymagnetic field- Pulse EN 61000-4-9 1000A/m, 1.2/50 μsmagnetic field8.2.1. Electrical safety testsTest Standard & Test class / level Test value- Impulse voltage EN 60255-5, class III 5 kV, 1.2/50 μs, 0.5 Jwithstand- Dielectric test EN 60255-5, class III 2 kV, 50 Hz- Insulation EN 60255-5resistance- Protective EN 60255-27bondingresistance- Power supply IEC 60255-1burden