Specifications18 Eaton 9170+ Battery Charger Module (Models ASY-0652 and ASY-0675) User’s Guide 164201399 —Rev F www.eaton.com/powerquality2 6/4200 60/59/58/57/56A 30/29/28/26/25A 80A 1145W(3.90 kBTU/hr)3 6/4200 76/75/74/73/72A 30/29/28/26/25A 100A 1430W(4.88 kBTU/hr)4 6/4200 92/91/90/89/88A 30/29/28/26/25A 125A 1720W(5.85 kBTU/hr)5 6/4200 102A* 30/29/28/26/25A 125A 1995W(6.75 kBTU/hr)0 9/6300 42/40.5/39/37.5/36A 45/43.5/42/39/37.5A 60A 860W(2.93 kBTU/hr)1 9/6300 58/56.5/55/53.5/52A 45/43.5/42/39/37.5A 80A 1145W(3.90 kBTU/hr)2 9/6300 74/72.5/71/69.5/68A 45/43.5/42/39/37.5A 100A 1430W(4.88 kBTU/hr)3 9/6300 90/88.5/87/85.5/84A 45/43.5/42/39/37.5A 125A 1720W(5.85 kBTU/hr)4 9/6300 102A* 45/43.5/42/39/37.5A 125A 1995W(6.75 kBTU/hr)0 12/8400 56/54/52/50/48A 60/58/56/52/50A 80A 1145W(3.90 kBTU/hr)1 12/8400 72/70/68/66/64A 60/58/56/52/50A 100A 1430W(4.88 kBTU/hr)2 12/8400 88/86/84/82/80A 60/58/56/52/50A 125A 1720W(5.85 kBTU/hr)3 12/8400 102/102/100/98/96A* 60/58/56/52/50A 125A 1995W(6.75 kBTU/hr)0 15/10500 70/67.5/65/62.5/60A 75/72.5/70/65/62.5A 100A 1430W(4.88 kBTU/hr)1 15/10500 86/83.5/81/78.5/76A 75/72.5/70/65/62.5A 125A 1720W(5.85 kBTU/hr)2 15/10500 102/99.5/97/94.5/92A* 75/72.5/70/65/62.5A 125A 1995W(6.75 kBTU/hr)0 18/12600 84/81/78/75/72A 90/87/84/78/75A 125A 1720W(5.85 kBTU/hr)1 18/12600 100/97/94/91/88A* 90/87/84/78/75A 125A 1995W(6.75 kBTU/hr)Table 4. Model Specifications for Universal Power Modules (ASY-0528 and ASY-0674) (Continued)Three-Slot CabinetOptionalChargersUPSkVA/WattsInput Current for200/208/220/230/240VOutput Current for200/208/220/230/240VRecommendedInput ServiceHeatDissipation* Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinetASY-0739.