Pro-Flood LED FloodlightnPFM Series 25L Industrial LED FloodlightInstallation & Maintenance InformationSAVE THESE INSTRUCTIONS FOR FUTURE REFERENCEIF 1684APPLICATIONPro-Flood LED Floodlights construction is designed for use indoors andoutdoors in marine and wet locations, where moisture, dirt, corrosion,vibration and rough usage may be present.• IEC 60598-1 and IEC 60598-2-1• Wet Locations• IP66Pro-Flood LED Floodlights are supplied for use with a choice of voltages:• 100VAC – 277VAC, 50/60Hz and 108VDC – 250VDC• 277VAC - 480VAC, 50/60HzWIRINGWiring the Floodlight1. All components in the fixture are prewired so only line in, neutral, andground need to be connected in the fixture to the terminals per thewiring diagrams using methods that comply with all applicable codes.Use supply cord with outer sheath diameter in accordance with Table 1.Terminate the equipment grounding conductor (green) first, the common(white) next, and finally, the line voltage (black) last. Secure all electricalconnections and wiring entry glands.Figure 1LED CIRCUIT BOARD+ -LED CIRCUIT BOARD+-NEUTRAL (WHT)LINE IN (BLK)LED CIRCUIT BOARD+ -LED CIRCUIT BOARD+-HOUSINGGROUND (GRN)DRIVERINPUT OUTPUTLINE IN (BLK)NEUTRAL (WHT) V+ (RED)V- (BLK)GROUND (GRN)DRIVERINPUT OUTPUTLINE IN (BLK)NEUTRAL (WHT) V+ (RED)V- (BLK)GROUND (GRN)GROUND TOHOUSINGFILTERTERMINALBLOCK ORLEVERLOCKSFigure 2 - Wiring DiagramGland Name PFM25L Ordering Suffix Thread Type Cable Diameter RangeCAP816604 M20 M20 x 1.5 8.5 - 16.0 mm (0.34 - 0.62 in)CAP816794 M25 M25 x 1.5 8.5 - 16.0 mm (0.34 - 0.62 in)Table 1INSTALLATIONMountingYOKE MOUNT - POST MOUNT USING FLOODLIGHT YOKE ONLY1. Select a durable, corrosion resistant mounting surface capable ofsupporting the fixture’s 50 lb (22.7 kg) weight and cantilevered mass (asapplicable).2. Using the floodlight yoke as a template, mark and drill desired location onmounting surface.3. Secure floodlight yoke to mounting surface by applying proper torque tocorrosion resistant 1/2inch (12mm) bolts or lag screws accompanied bylock washers.4. Ensure that the safety chain is securely fastened between the yokebracket and back cover.IF 1684 • 04/22 Copyright © 2022, Eaton’s Crouse-Hinds Division Page 1WARNINGTo avoid potentially unsafe harm to eyes:Mount at a minimum recommended height of 20ft (6m) - 7x6 optic,60ft - 3x3 optic.Directive EU 2019/2022This product contains a light source of energy efficiency class D or E.To avoid the risk of fire, explosion, or electric shock, this productshould be installed, inspected, and maintained by a qualified electricianonly, in accordance with all applicable electrical codes.WARNING!To avoid electric shock:Be certain electrical power is OFF before and during installation andmaintenance.To avoid burning hands:Make sure lens and housing are cool when performing maintenance.WARNING!WARNINGTo avoid potentially unsafe operating conditions:Before opening, electrical power to the floodlight must be turned off.Keep tightly closed when in operation.Make sure the supply voltage is within the floodlight voltage range statedon the nameplate.Do not operate in ambient temperatures above those indicated on thefloodlight nameplate.Use only replacement parts from Eaton’s Crouse-Hinds Business.Use proper supply wiring as specified on the floodlight nameplate.All gasket seals must be clean, and properly positioned.Do not position the floodlight beyond the aiming range limits.Do not exceed the maximum allowable current draw of 15 Amps whendaisy chaining floodlights, (S886 configuration only).!!