I.L. 66A7508H05 Page 17Effective September 2003Control Group Definition Byte2 Byte1 Byte0Reset alarm 0 0 1Reset trip 0 0 2Reset (peak) demand-watts 0 0 4Reset energy (kilowatt hours) 0 0 8Reset device software 0 0 16 (1016 )Reset time stamped event data buffers 0 0 32 (2016 )Reset (synchronize) demand watts window 0 0 64 (4016 )Snapshot command 0 0 128 (8016 )Reset (peak) demand-currents 0 1 1Reset operations count (or trigger counters) 0 1 2Reset run time 0 1 3Reset all min/max values 0 1 4Unlock waveform buffer (clear upload-in-progress) 0 1 5Reset discrete input counters 0 1 6Reset min/max currents 0 1 13Reset min/max L-L voltages 0 1 14Reset min/max L-N voltages 0 1 15Reset min/max PF-apparent 0 1 16Reset min/max PF-displacement 0 1 17Reset min/max power 0 1 18Reset min/max current THD 0 1 19Reset min/max voltage THD 0 1 20Reset min/max per-phase power 0 1 22Reset op count, runtime & override count 0 1 36Reset motor data maximum values 0 1 37Reset motor trip & alarm counters 0 1 38Reset locked-trigger # X (X = trigger number) 0 2 XReset source 1 available time 0 3 1Reset source 1 connect time 0 3 2Reset source 1 run time 0 3 3Reset source 2 available time 0 3 4Reset source 2 connect time 0 3 5Reset source 2 run time 0 3 6Reset load energized time 0 3 7Reset transfer status 0 3 8ResetReset tamper flag for sensor #X 0 4 XOpen request 1 0 0Close request 1 0 1Circuit BreakerOpen-Close Trip request 1 0 2No action 2 0 0Start fast forward 2 0 1Start fast reverse 2 0 2Stop 2 0 3Start 2 0 4Start slow forward 2 0 5Start slow reverse 2 0 6Set direction to forward 2 0 7Set direction to reverse 2 0 8MotorStart-StopEmergency override 2 0 10Table 12: Control 'Slave Action Number' Definitions