8. Trouble shootingIn most situations, the Inverter requires very little service. However, ifInverter is not able to work perfectly, please refer to the following instructionsbefore calling your local dealer.z Should any problems arise, the red (Fault) LED on the front panel turnson and the LCD displays the relevant information. Please refer to thefollowing table for a list of potential problems and their solutions.Display Possible actionsIsolation Fault1. Check the impedance is between PV (+) & PV(-) and the PV-Inverter is earthed. Theimpedance must be greater than 5MΩ2. If the problem persists please contact Eaton.Ground I Fault1. The ground current is too high.2. Unplug the inputs from the PV generator andcheck the peripheral AC system3. After the cause is cleared, re-plug the PV paneland check PV-Inverter status.4. If the problem persists please contact Eaton.Grid Fault1. Wait for 5 minutes, if the grid returns to normal,PV-Inverter automatically restarts.2. Make sure grid voltage and frequency meet thespecifications3. If the problem persists please contact Eaton.SystemFaultNo Utility1. Grid is not connected.2. Check grid connection cables.3. Check grid usability.PV overVoltage1. Check the open PV voltage, see if it is greaterthan or too close to 450VDC2. If PV voltage is less than 450VDC, and theproblem still occurs, please contact Eaton.InverterFailureConsistentFault1. Disconnect PV (+) or PV (-) from the input,restart the PV-Inverter2. If it does not work, please Contact Eaton.29