34007724EN/AD - Page 273. OperationPersonnalisation batterieUse EXIT key when set up is completed.zThese parameters are only adjustable ifz UPS is OFF.Access to the personalisation through external softwareInsert thez Solution-Pac CD ROM in your CD drive.At the first Navigator Screen, select "Installation" and follow the instructions to installz PersonalSolution-Pac for Windows.If nothing appears, launch startup.exezThen go to "Advanced settings" and "UPS settings".zPlease note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.3.2 Final start up sequencePress the ON button more than 3 seconds.zAfter UPS internal test sequence, the green LEDz 13 goes on.During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibratedbreak.ON/OFF featuresFunction Factory setting Options CommentsCold start Disabled Enabled Start on battery.Forced reboot Enabled Disabled Enables automatic restart of the systemeven if normal AC source is restored beforethe end of the shutdown sequence.Automatic restart Enabled Disabled UPS restarts automaticallywhen normal AC source is restored.Sleep mode Disabled Enabled Automatic shudown on battery if outputload level < 10%.UPS ON/OFF by software Enabled Disabled Enables consideration of shutdownor restart orders from software to beauthorized.Function Factory setting Options CommentsBattery test Every week No test / daily / monthlyLow battery signal 20 % 0 to 100 % 1% increment.Run time choice UPS reads # of batterymodules connectedFrom 50 to 400 Ah Requires EX RT CLA if usingoptions (see section 1.4"Battery extensions").Battery deep dischargeprotectionEnabled Disabled If disabled, lost of EATONwarranty.