Eaton Industries Canada Company10725 25th Street NE, #124Calgary, ABCanada T3N0A4www.chfire.comTechnical Data MN081024ENQuick Setup Programming GuideEffective June 2015© 2015 EatonAll Rights ReservedPrinted in CanadaPublication No. MN081024ENJune 2015Jockey Pump ControllersSTART PRESSUREThe pressure is set in PSI format.(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)Using the number buttons, enter the start pressure.Pressing the Arrow button will delete the pressure values one character at a time.Once the pressure is programmed, press the Next button.Pressing the Cancel button will return the display to the Panel Setup 1/2 screen.All Quick Setup values must be re-entered.STOP PRESSUREThe pressure is set in PSI format.(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)Using the number buttons, enter the stop pressure.Pressing the Arrow button will delete the pressure values one character at a time.Once the pressure is programmed, press the Next button.Pressing the Cancel button will return the display to the Panel Setup 1/2 screen.All Quick Setup values must be re-entered.MINIMUM RUN TIMERThe minimum run time can be set up to 999 seconds.The timer can be disabled by pressing the button.To re-enable the timer, press the Arrow button.(The timer values are erased and must be re-entered).Using the number buttons, enter the minimum run time.Pressing the Arrow button will delete the timer values one character at a time.Once the minimum run time is programmed, press the Next button.Pressing the Cancel button will return the display to the Panel Setup 1/2 screen.All Quick Setup values must be re-entered.SETUP COMPLETEOnce all the functions have been set, press the OK button.The display will return to the Main Display Screen.Pressing the Cancel button will return the display to the Panel Setup 1/2 screen.All Quick Setup values must be re-entered.SET DATEThe date is set in MM/DD/YY format.Using the number buttons, enter the current date.Pressing the Arrow button will delete values one character at a time.Once the date is programmed, press the Next button.This will advance the screen to the Quick Setup screen for setting the Start Pressure.Pressing the Cancel button will return the display to the Panel Setup 1/2 screen.All Quick Setup values must be re-entered.