Page 18 SK-90610-Y4_EN6. SpecificationsMBP6K208 MBP11K208InputTerminal blocksOutput2 L6-30R + Terminal blocks 3 L6-30R + Terminal blocksOverall dimensions D x W x H (inch / mm)5.6 x 7.0 x 5.1 /142 x 177 x 13010.2 x 13.2 x 5.1 /260 x 336 x 130Weight (lb / kg)5.5 / 2.5 13.7 / 6.2PerformanceNominal voltage 200 - 240 V ~ 200 - 240 V ~Frequency 50/60 HzInput nominalcurrent24A 50AMaximal power 6000 VA 11000 VAStandards (HotSwap MBP used with UPS)Safety IEC/EN 62040-1 / Ed.1: 2008. UL 1778 4 th edition.EMC IEC 62040-2 / Ed.2: 2005. EN 62040-2 / Ed.2: 2006. FCC part 15 Class A.Performance IEC/EN 62040-3 / Ed.2.0: 2011.ESD IEC 61000-4-2 : level 3.Radiated field IEC 61000-4-3 : level 3.EFT IEC 61000-4-4 : level 4.Fast transients IEC 61000-4-5 : level 4.Electromagnetic field IEC 61000-4-6 : level 3.Conductedmagnetic fieldIEC 61000-4-8 : level 4.MarkingcULus Listed / CEEnvironmentOperatingtemperature0 to 40°C (32 to 104°F)Storage temperature -15 to 60°C (5 to 140°F)Transit temperature -25 to 55°C (-13 to 130°F)Humidity 0 to 95% no condensingOperation Altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000mTransit Altitude Up to 10,000 meters (32,808 ft) above sea levelRecommended upstream protectionUPS power rating Upstream circuit breaker5000VA D curve - 30A6000VA D curve - 30A8000VA D curve - 50A11000VA D curve - 70AG N(L2) L1N(L2) to UPS Normal AC source2 poles circuit breakerL1