I.B. 2C12060H08 For more information visit: www.EatonElectrical.comInstruction BookPage 25Effective: May 2006Figure 3-26 Connection Diagram for Narrow and Standard Frame with Digitrip 520 and 520M (except Narrow 100kAratings)NOTES:1. 4 WIRE CRIMP CONNECTION2. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED.3. WIRE CONNECTION USED WITH DIGITRIP 520M/520MC GROUND ALARM POWER SUPPLY MODULE WILL “HANG UNCON-NECTED” IF DIGITRIP 220 OR 520 IS SUPPLIED.4. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP UNITIN “NON-TRIPPED” STATE (OTS SWITCHES).5. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO-VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FORSUBSEQUENT OPERATION.AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED)LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED ANDRESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASEPULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHENTHE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRINGRELEASE FOR SUBSEQUENT OPERATION.6. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.7. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY, A JUMPER INSTALLED FROM B-6 TO B-7WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS B-4 AND B-5WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.8. THIS LEAD SUPPLIED ON G62 STYLE HIGH INSTANTANEOUS TRIP MODULE ONLY.9. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.10. ON 4-POLE BREAKERS, THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND WIRED THE SAME AS THE PHASESENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CONTACTS B-4, B-5, ARE NOT WIRED OUT.11. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOTAVAILABLE WITH SECOND SHUNT TRIP.12. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-29,B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3 FORSPRING RELEASE LATCH CHECK SWITCH.13. THIS AUX. SWITCH ASSEMBLY NOT AVAILABLE IN NARROW FRAME. MAXIMUM OF TWO AUX SWITCHES (4A/4B)INSTALLED IN NARROW FRAME.SEE NOTE 13www . ElectricalPartManuals . com