MEMSHIELD 4 INSTALLATION INSTRUCTIONS FOR 800A PANELBOARDS / PAN ASSEMBLIESEM4PB680, EM4PB1280, EM4PB1680EM4PBP680, EM4PBP1280, EM4PBP1680Instruction Leaflet LT1223 (02/19)800A Incoming MCCB EM4PBK804TransitmountdiscardRemovefor accessFitIncomingMountIncoming Modules3 Pole & Neutral - Bottom EntryForm 4 Type 6 Group MountedSecureallshields800A Incoming Direct Cable EM4PBK804L MCCB Incoming CoverKnockout RemovalDo not remove for direct cableincomerRemove for Bottom Entry 3 pole and NRemove for Bottom Entry 4 polePanelboards are supplied as Bottom Entry and Form 4 Type 6 Group Mounted without modificationGeneral Note: When fixing M5 thread formingscrews tightening torque is 3.8 Nm4 Pole -Bottom EntryForm 4 Type 6SecureallshieldsIMPORTANT NOTES1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician inaccordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring RegulationsBS7671), Construction (Design and Management) Regulations, HSG150 ā Health and Safety in Construction, Statutory requirementsand any Specific instruction issued by the Company.2. After completing the installation and testing of this product it is essential that this leaflet is drawn to the attention of the personresponsible for its future operation and maintenance, and is at all times available for ready reference.3. The notes assume throughout that the product is disconnected from the supply. It is essential that this is done before any work iscarried out.4. These Panelboards are only designed for use with EATON MCCBs. Failure to comply will result in invalid warranty and certification.BottomEntry800A Incoming Neutral EM4PBNK804 Pole - Bottom EntryForm 4 Type 6 Group MountedSecureallshields30NmTransitmountdiscardRemovefor accessFitMount46Nm30Nm30NmFitInterphaseshields46NmFit shieldFit neutral