INTEGRATING THE UPSEATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com185. Run profiler from the command prompt or double-click profiler.exefrom Microsoft Windows Explorer.By default, Modbus Profiler uses the communication port specifiedin the [Connection] section of the profiler.ini file. If profiler fails toconnect using this communication port, you are prompted with alist of alternate communication ports. You may also edit the Port=value in the [Connection] section of the profiler.ini file to change thedefault value.6. Modbus Profiler creates an output file named profiler.csv in thedirectory where the Modbus Profiler tool is located.Before the program exits, you are prompted to view the data.The comma delimited file can be easily imported into MicrosoftExcel for viewing of the Modbus data. This data is used to createthe necessary template files on your Building Management Systemfor polling the desired UPS information.NOTE Modbus Profiler does not provide Modbus data for the Powerware 9315 Series UPS.Powerware 9315 configuration-specific profiles are available in the directory where theModbus Profiler tool is located (refer to the 950*.pdf files).Example Modbus Profiler Output FilesThe following tables are sample Modbus Profiler output files for aPowerware 9315 Reverse Transfer (RT) Single Module UPS. Refer to theMaster Modbus Register Map for a complete list of the Status, Alarm,and Meter data for all Powerware UPS equipment (open thereg_map.pdf file in the directory where the Modbus Profiler tool islocated).Table 4. Read Input Status - Modbus Function Code 02 (Inputs Start at 10000)Register Name Value Format Unit1 On Battery 0 BOOL Status10 On Bypass 1 BOOL Status11 System Normal 0 BOOL Status16 UPS Off 0 BOOL StatusNOTE Registers 1–16 are mutually exclusive.112 Rectifier Status 1 BOOL Status