7*. The maximum current can be obtained when the UPS input is 187V, output is underrated full load, and charger works under full load.*. When output voltage is adjusted from 220V to 200V or 208V, the rated power of outputVA and WATT should be decreased by 10%.* . T h e o u t p u t v o l t a g e i s a d j u s t a b l e a c c o r d i n g t o c u s t o m e r r e q u i r e m e n t s(200/208/220/230/240 VAC).Altitude (m) 1000 1500 2000 2500 3000 3500 4000 4500 5000Coefficient 100% 95% 91% 86% 82% 78% 74% 70% 67%CAUTION: It needed to reduce the power of output when the products are used in ahigh altitude above 1000m, the coefficient for the actual power refer to the foregoingtable.Actual power (all Load capacity) = rated power * coefficient (correspond to the altitude)