Siemens APOGEE™ FLN (P1) Communication KitMN04008002E For more information visit: www.EatonElectrical.com 4-1February 2006Chapter 4 — CommissioningFieldbus Board ParametersThe RS-485 Communication Board (OPTCB) is commissioned with the control keypad bygiving values to appropriate parameters in the Expander board menu M4.Expander Board Menu (M4)The Expander board menu makes it possible for the user (1) to see what expander boards areconnected to the control board, and (2) to view and edit the parameters associated with theexpander board.Enter the following menu level (G4) with the menu button (right arrow). At this level, youcan browse through slots A to E with the Browser buttons to see which expander boards areinstalled. On the bottom line of the display, you also see the number of parameter groupsassociated with the board.If you press the menu button again, you will reach the parameter group level where thereare two groups: Editable parameters and Monitored values. Another press on the menubutton takes you to either of these groups.Siemens FLN Communication ParametersTo commission the Siemens FLN Communication Board, enter the level P4.5.1.# from theExpander Board Menu 4. The board can be installed in either slot D (G4.4) or slot E (G4.5). It isinstalled in slot E from the factory.Table 4-1: Changing the FLN Board Commissioning Parameter ValuesThe SLAVE ADDRESS of every device must be set before connecting to the bus. The SLAVEADDRESS must be the same as in the master configuration. The baud rate is automaticallyconfigured for 4800. No adjustment is possible.1. Review the following drive and fieldbus application parameter settings:● Check that application HVX9.11 or later is selected.Application Selection S3.2 = HVX9.11 or later versionRefer to the HVX9000 User Manual for instructions on how to set parameters usingthe keypad.● Check that start source auto is set to network. This allows the user to provide start/stop commands from the FLN network.Parameter P1.1.17 = Fieldbus● Check that reference source auto is set to network. This allows the user to providea speed reference from the FLN network.Parameter P1.1.18 = Fieldbus● Check that the HOA mode is set to AUTO.# Name Default Range Description1 CommunicationTimeout10 0 – OFF1 – 300 sSee Communication Timeout on Page 4-2.