5510/15 MN03402004Z-DE/EN8 Using the deviceSettings Before commissioning the PKE motor-protective circuit-breaker, the rated motor current must be set using thesetting dial on the PKE motor-protective circuit-breaker(a Table 9, Page 40). The setting dial on the trip block has16 detent positions. This makes the following settingspossible:Table 16: Overview of settings on trip blockTest The motor-protective circuit-breaker features a test function(a Figure 17, Page 44).When the test function is operated with the motor-protectivecircuit-breaker switched on, the PKE trips and all maincontacts open. The lines downstream of the PKE can then betested for zero voltage. To allow the powered-on PKE motor-protective circuit-breaker to trip in its test position, a currentcorresponding at least with the minimum set value of the tripblock must flow.To maintain a proper working state, repeated testing of elec-trical plants and equipment is necessary.0.3 - 1.2 A 0.30 0.33 0.36 0.40 0.43 0.47 0.50 0.560.63 0.70 0.77 0.83 0.90 1.00 1.10 1.201 - 4 A 1.00 1.10 1.20 1.30 1.42 1.55 1.70 1.902.10 2.40 2.60 2.80 3.00 3.30 3.70 4.003 - 12 A 3.00 3.30 3.60 4.00 4.30 4.70 5.00 5.606.30 7.00 7.70 8.30 9.00 10.00 11.00 12.008 - 32 A 8.00 8.80 9.70 10.50 11.50 12.50 13.50 15.0017.00 19.00 20.50 22.00 24.00 27.00 29.00 32.0016 - 65 A 16.00 17.50 19.50 21.00 23.00 25.00 27.00 30.0034.00 38.00 41.00 44.00 48.00 53.00 58.00 65.00j Danger!Faulty devices must not be opened and repaired. Theymust be replaced by specialist personnel.