36Cabinet dimensionsInstruction manual IM1002004E September 2015 www.powerquality.eaton.comCabinet dimensionsTable 6. Power-Sure 700 unit cabinet sizeskVArating Bypass MeteringCabinet sizeH x W x D (in) BTUs/Hr Weight (Lb)10 Yes No 30.2 x 22.2 x 29.0 1,025 44010 Yes Yes 44.2 x 22.2 x 29.0 1,205 52015 Yes No 30.2 x 22.2 x 29.0 1,540 46515 Yes Yes 44.2 x 22.2 x 29.0 1,540 70025 Yes Yes 44.2 x 22.2 x 29.0 2,560 70030 Yes Yes 44.2 x 22.2 x 29.0 3,090 72045 Yes Yes 44.3 x 45.9 x 29.0 4,600 95050 Yes Yes 66.0 x 29.0 x 35.5 7,332 1,17675 Yes Yes 76.0 x 34.4 x 35.5 9,514 1,575100 Yes Yes 76.0 x 34.4 x 35.5 11,833 2,014125 Yes Yes 76.0 x 34.4 x 35.5 14,748 2,137150 Yes Yes 76.0 x 34.4 x 35.5 17,698 2,240225 Yes Yes 77.4 x 56.0 x 41.5 23,000 3,300300 Yes Yes 77.4 x 56.0 x 41.5 30,750 4,000500 Yes Yes 77.0 x 72.4 x 48.4 51,250 5,500Manual bypass switchThe manual bypass switch is a break-before-make switchlocated on the Power-Sure 700. The manual bypass switchis used to bypass all power electronics in case of failure.Bypass is standard on 50 kVA and larger units and an optionon 45 kVA and smaller units.otes:N This switch may be added in the field.Normal modeWith the switch in the normal position, the Power-Sure 700will provide clean and regulated power to the critical loads.The Power-Sure 700 should have the switch in the normalposition unless a failure has occurred.These units are sold in accordance to EatonSelling Policy 25-000.