UPS Operating Instructions7-40 Power Xpert TM 9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10 www.eaton.com/powerquality18. Open the input and bypass feeder circuit breakers for the UPS being shut down.The UPS is now completely shut down.External Communications Failure alarm is active on remaining online UPSs. This is an expected event andwill clear upon UPS restart.7.4.24 Single UPS RestartTo restart a single UPS from a shutdown state:1. Close the MOB for the UPS being restarted.2. Close UPS input and bypass feeder circuit breakers for the UPS being restarted.3. Unfasten the front door latch and swing the door open on the UPS being restarted (see Figure 4-2).4. If input breaker (CB1) is installed on the UPS being restarted and is open, close the breaker.5. Close the door and secure the latch.6. On the UPS being restarted, observe the UPS control panel display becoming active, indicating logicpower.7. On the UPS being restarted, press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.8. On the System Status screen, verify the UPS status is SHUTDOWN and the UPM status is SHUTDOWN.9. Close the battery breaker for the UPS being restarted.10. Verify no alarms are active on UPS being restarted.11. Verify the External Communications Failure alarm has cleared and no other alarms are active on the onlineUPSs.12. On the System Status screen, select the UPS command.13. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen isdisplayed.14. On the UPS Control Command screen, select GO TO ONLINE.15. Press the SELECT pushbutton on the UPS Command menu bar.16. Verify the following messages display sequentially on the UPS status line:DC STARTING, CHARGER OFFINVERTER STARTINGINVERTER SYNCINGONLINE, CHARGER ONThe rectifier and inverter turn on. The inverter continues to ramp to full voltage.Once the inverter reaches full voltage, the UPS output contactor (K3) closes. Power is now supplied to thecritical load in Online mode along with the other UPSs online. It takes approximately one minute for theUPS to achieve Online mode.The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicatesONLINE, CHARGER ON.7.4.25 UPS and Critical Load ShutdownTo perform maintenance or service on the critical load, shut down power to the load:1. Turn off all equipment that is being powered by the distributed bypass system.NOTE If the UPS is starting on a bus with other online paralleled UPSs, the UPS will not goto bypass during startup. The UPS will start, sync to the other UPSs online, and goonline.