Product Specifications10-2 Eaton ® Power Xpert® 9395C UPS Installation and Operation Manual P-164000821—Rev 01 www.eaton.com/powerquality10.2.2 UPS Output10.2.3 UPS Environmental10.2.4 Battery RunTime RatingsUPS Output Capacity 100% rated currentOutput Voltage Regulation ±1.5% (10% to 100% load)Output Voltage(Nominal +/–3%)480 Vac nominal, adjustable from 466 Vac to 494 VacOutput Voltage Harmonic Content 1% maximum THD (linear load)5% maximum THD (nonlinear load)Output Current See Table 3-4Output Voltage Balance 2.5% for 100% maximum load imbalance (linear load)Output Voltage PhaseDisplacement±4° for 100% maximum load imbalance (linear load)Output Transients Meets Class 1 IEC 62040-3 (10% to 100% load)Frequency Regulation ±0.1 Hz free runningSynchronous to Bypass +10% to -10%Frequency Slew Rate .7 Hz per second maximumLoad Compatibility 0.9 pF Leading0.7 pF LaggingOverload Capability (kVA or kW) 110% for 10 minutes125% for 120 seconds150% for 15 secondsNOTE The 125% and 150% overloads are based on the non-derated hardware capability of the UPS.Operating Temperature 0 to 40°C (32 to 104°F) at elevation up to 1000m without derating.The recommended operating temperature is 25°C (77°F).Operating Altitude Maximum 1000 m (3300 ft) at 40°C without deratingStorage Temperature –25 to +60°C excluding batteries (prolonged storage above 40°C causesrapid battery self-discharge)Relative Humidity (operating and storage) 5% to 95% maximum noncondensingAgency Markings 78 dB at a 1m distance, A weighted for one UPSEMI Emissions and Immunity Meets IEC 62040-2, category C3Electrostatic Discharge (ESD) Immunity Meets IEC 801-2 specifications. Withstands up to 25 kV pulse withoutdamage and with no disturbance or adverse effect to the critical load.kVA kW AmbientTemperatureBatteryRuntime(minutes)1100 1100 35°C (95°F) 121100 1000 40°C (104°F) 201000 1000 40°C (104°F) 20NOTE Timer will be disabled below 700kW