SPECIFICATIONSEATON Powerware® 5125 Two-in-One UPS (1000–1500 VA) User’s Guide S 05147305 Rev D www.power-ware.com44Table 4. Technical SpecificationsLow Voltage Models High Voltage ModelsOperating Frequency 50/60 Hz, auto-sensingFrequency Range 46–65 HzNoise Filtering MOVs and line filter for normal and common mode noiseInput Connections 6-ft, 5-15P power cordPW5125 1500j RM: 6-ft, 5-20P power cord10A, IEC-320 input connectorRegulation(Normal Mode)-10% to +6% of nominal voltageRegulation(Battery Mode)Nominal output voltage ±5%Voltage Waveform Sine waveOutput Receptacles (6) 5-15R (6) 10A, IEC 320-C13Table 5. Environmental and SafetyLow Voltage Models High Voltage ModelsOperating Temperature 0°C to 40°C (32°F to 104°F)Optimal battery performance: 25°C (77°F)Storage Temperature 0°C to 25°C (32°F to 77°F)Transit Temperature -25°C to 55°C (-13°F to 131°F)Relative Humidity 5–95% noncondensingOperating Altitude Up to 3,000 meters above sea levelTransit Altitude Up to 15,000 meters above sea levelAudible Noise Less than 40 dBA Normal mode, typical loadLess than 55 dBA Battery modeSurge Suppression ANSI C62.41 Category B, IEC 61000-4-5Safety Conformance UL 1778, UL 497A;CSA C22.2, No. 107.1;NOM-019-SCFIUL 1778, UL 497A (data line only);CSA C22.2, No. 107.1;EN 50091-1-1 and IEC 60950Agency Markings cULus, cUL, NOM cULus and cUL; CE, C-Tick, LGA/GS, DEMKOEMC (Class A) FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003