INSTALLATIONEATON Powerware® 9125 Two-in-One UPS (5000/6000 VA) User’s Guide S 164201513 Rev Bwww.powerware.com227. Plug the UPS power cord into an L6-30R power outlet.The μ indicator flashes, indicating the UPS is in Standby modewith the equipment offline.8. Press the On button (see Figure 14 on page 31).The μ indicator illuminates solid and the bar graph indicatorsdisplay the percentage of load being applied to the UPS. The UPS isnow in Normal mode and supplying power to your equipment.The UPS automatically sets the output voltage based on the inputvoltage. To change the output voltage, see “Configuration” onpage 35.NOTE The batteries charge to 80% capacity in less than 2 hours. However, it isrecommended that the batteries charge for 24 hours after installation or long-term storage.NOTE If you installed power management software and optional EBMs, ensure maximumbattery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD.Remote Emergency Power-off InstallationThe Powerware 9125 includes a REPO connector that allows power tobe switched off at the UPS output from a customer-supplied switch in aremote location.The REPO feature shuts down the protected equipment immediatelyand does not follow the orderly shutdown procedure initiated by anypower management software.Any devices that are operating on battery power are also shut downimmediately. When the REPO switch is reset, the equipment will notreturn to battery power until the UPS is manually restarted.If the Off button is pressed after the REPO is activated, the UPSremains in Standby mode when restarted until the On button ispressed.