Operation6 Eaton 93PM Remote Monitoring Device (RMD) Installation and Operation Manual P-164000516—Rev 1OperationThis section describes how to operate the RMD.RMD ComponentsThe components identified and described in this section are used to connect and operate the RMD.l 4.3” Display Screen – shows UPS statusl Power Pushbutton – turns the RMD on (press and hold for 3 seconds) and off (press and hold for11 seconds) and is used to silence the audible alarml Audible Alarm – the alarm sounds to alert an operator that an event needing attention is taking place. Tosilence the audible alarm, press the power button momentarily (see Figure 4)l Micro USB Connector – connects the external charger to RMD internal batteryl Ethernet Connector – connects the RMD to the UPS PXGMS cardFigure 4 shows the location of the RMD components.Display Screen SectionsThe display consists of two sections, a status indicator section on the left side of the screen and an informationarea to the right of the status indicators that displays operational messages. The status indicator icons displayas green, yellow, or red depending on the status of the UPS. Figure 5 shows the display screen sections.l Input – This icon shows the state of the incoming power. It is green if the power is available and good. If itturns yellow the voltage or frequency of the electrical power is not within acceptable limits.l Battery – This icon shows the state of the energy storage and charge percent. Each bar of the Battery iconrepresents a predefined percentage of the total energy as follows: if five bars are shown the energy chargeis between 90-100%; if four bars are shown the charge is between 70-89%; if three bars are shown thecharge is between 50-69%; if two bars are shown the charge is between 30-49%; if one bar is shown thecharge is between 10-29%; if no bars are shown the charge is 9% or less. In case the input power fails, andthe UPS goes on battery, this icon will turn yellow. When the battery is almost depleted and there are only afew minutes of runtime left the icon will turn red.l Bypass – Under normal operation this icon should remain green. If it changes to yellow, the UPS is onbypass and is not able to provide battery backup.l Alarm – Under normal operation this icon should remain green. If it changes to yellow or red, there may bean issue with the UPS. Check the UPS and its local display for details.Battery IconNumber of Bars Displayed Energy ChargeFive 90-100%Four 70-89%Three 50-69%Two 30-49%One 10-29%None 9% or less