Connecting the power supply1507/09 MN03407002Z-ENFigure 9: Connecting the power supplyThe terminals are suitable for AWG22 to AWG16 cables andfor flexible cables with a cross-section of 0.5 to 1.5 mm².Tighten the terminals to 06 Nm.24V0.6 x 3.5L01+L01–1 A 3 AUe = 24 V H(20.4 – 28.8 V H)0V24V 0V0.6 Nmh The gateway is protected by a 1 A gG/gL line protectionfuse or a 1 A miniature circuit-breaker featuringcharacteristic C. The fusing of the incoming supply for thecontactor coils is implemented using 3 A gG/gL fuses or a3 A miniature circuit-breake featuring characteristic Z.j Danger!In safety-relevant applications the power supply providingpower to the SmartWire system must feature a PELVpower supply unit (protective extra low voltage).